94 FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
… 8 Operation
… Parameter descriptions
Menu: Process Alarm
Menu / parameter Description
Process Alarm
Alarm history Display of the alarm history
Clear Alarm History Reset of the alarm history.
...Group Masking Selection of submenu ‘...Group Masking’ using .
...Alarm Limits Selection of submenu ‘...Alarm Limits’ using .
Process Alarm / ...Group Masking
Maintenance Required Alarm messages are divided into groups.
If masking is activated for a group (On), no alarm is issued.
For additional information, see Diagnosis / error messages on page 109.
Function Check
Out Of Specification
Process Alarm / ...Alarm Limits
Qm Massflow Min Set the minimum / maximum limit value (0 to 110 %) for mass measurement. If the process value ‘Qm [unit]’ exceeds or falls
below the limit value, an alarm is triggered.
Qm Massflow Max
Qv Volumeflow Min Set the minimum / maximum limit value (0 to 110 %) for volume measurement. If the process value ‘Qv [unit]’ exceeds or
falls below the limit value, an alarm is triggered.
Qv Volumeflow Max

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ProcessMaster FEP630 series and is the answer not in the manual?

ABB ProcessMaster FEP630 series Specifications

General IconGeneral
BrandABB
ModelProcessMaster FEP630 series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals