Settings and configuration
Chapter 7
88
1SFC132003M0201
Setting I
e
Set the current that the softstarter will be exposed to i.e.
rated motor current if the unit is connected In Line.
For units connected Inside Delta the Setting I
e
must be set
according to the current in the delta circuit = 58% ( )
of the rated motor current.
Press Store to save the data after setting the current.
Confirm the Setting I
e
by pressing Next. If wrong Setting I
e
was set, press Back and set the correct value.
Overload class (OL Class)
Select the class for the overload relay for the used
application type. Available classes:
10A
•10
•20
30
Press Store to save the selected class.
Confirm the selected overload class by pressing Next. If
wrong overload class was selected, press Back and select
the correct class.
External By-Pass contactor (Ext ByPass)
If an external by-pass contactor is used, set the parameter to
Yes, otherwise No.
Press Store to save the data.
Confirm the selection of external by-pass by pressing Next. If
wrong selection was made, press Back and correct the
selection.
Tune Set
The configuration of the application setting menu is now
completed. If no tuning of the settings is wanted, it is possible
to return to the top level by pressing Yes.
If tuning of some main parameters is wanted, select Tune
Set.
Setting Ie 100A
Store
F
igure 16: Setting Ie menu
13()
Setting Ie 100A
Next Back
Figure 17: Confirming Setting Ie
OL Class 10
Store
F
igure 18: Overload class
OL Class 10
Next Back
Figure 19:Confirming OL Class
Ext ByPass Yes
Store
Figure 20: External ByPass
Ext ByPass Yes
Next Back
Figure 21:Confirming Ext ByPass
Ready?
Yes Tune Set
Figure 22:Ready?/Tune Set menu