Settings and configuration
Chapter 7
98
1SFC132003M0201
Underload protection (Underload)
Activate the protection if required by changing to Yes.
If “Yes” is selected, the following settings will be
available:
Underload level (Underl Lev)
Set the level of the underload protection.
Available only if the protection is selected.
Underload time (Underl Time)
Set the time for the underload protection.
Available only if the protection is selected.
Underload type of operation (Underl Op)
Select what operation shall be asserted if the underload
protection is activated:
Stop–M The motor will stop and a manual reset is
required.
Stop–A The motor will stop and automatic reset is
performed.
Ind Only indication will be given.
Press Store to save the selected operation.