Settings and configuration
Chapter 7
99
1SFC132003M0201
Phase imbalance protection (Phase Imb)
Activate the protection if required by changing to Yes.
If “Yes” is selected, the following settings will be
available:
Phase imbalance level (Ph Imb Lev)
Set the level of the phase imbalance protection.
Available only if the protection is selected.
Phase imbalance type of operation (Ph Imb Op)
Select what operation shall be asserted if the phase
imbalance protection is activated:
Stop–M The motor will stop and a manual reset is
required.
Stop–A The motor will stop and automatic reset is
performed.
Ind Only indication will be given.
Press Store to save the selected operation.
High current protection (High I)
Activate the high current protection if required by changing to
Yes.
If “Yes” is selected, the following setting will be
available:
High current type of operation (High I Op)
Select what operation shall be asserted if the high current
protection is activated:
Stop–M The motor will stop and a manual reset is
required.
Stop–A The motor will stop and automatic reset is
performed.
Ind Only indication will be given.
Press Store to save the selected operation.