S TD S TD S
Old Calculated
= +
( )
1
EQUATION1893-ANSI V1 EN-US (Equation 88)
Where
S is a new measured value to be used for the protection function
S
old
is the measured value given from the function in previous execution cycle
S
Calculated
is the new calculated value in the present execution cycle
TD is settable parameter
The value of TD=0.92 is recommended in generator applications as the trip delay is
normally quite long.
The calibration factors for current and voltage measurement errors are set % of rated
current/voltage:
IMagComp5, IMagComp30, IMagComp100
VMagComp5, VMagComp30, VMagComp100
IAngComp5, IAngComp30, IAngComp100
The angle compensation is given as dif
ference between current and voltage angle
errors.
The values are given for operating points 5, 30 and 100% of rated current/voltage. The
values should be available from instrument transformer test protocols.
8.14 Broken conductor check BRCPTOC
(46)
SEMOD171761-1 v3
8.14.1 Identification
SEMOD172362-2 v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Broken conductor check BRCPTOC - 46
Section 8 1MRK 511 401-UUS A
Current protection
226 Bay control REC670 2.2 ANSI
Application manual