Figure 17: Delta DAC connected three-phase CT set
In this case, everything is done in a similar way as in the above described example,
except that for all used current inputs on the TRM the following setting parameters
shall be entered:
CT
prim
=800A
CT
sec
=1A
CTWyePoint=ToObject
ConnectionType=Ph-Ph
It is important to notice the references in SMAI. As inputs at Ph-Ph are expected to be
A-B, B-Crespectively C-A we need to tilt 180º by setting ToObject.
4.2.2.7 Example how to connect single-phase CT to the IED
SEMOD55055-431 v8
Figure
18 gives an example how to connect the single-phase CT to the IED. It gives an
overview of the required actions by the user in order to make this measurement
available to the built-in protection and control functions within the IED as well.
Section 4 1MRK 511 401-UUS A
Analog inputs
76 Bay control REC670 2.2 ANSI
Application manual