EasyManua.ls Logo

ABB rec670 - Interlocking for Double CB Bay DB (3)

ABB rec670
658 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.4.8 Interlocking for double CB bay DB (3)
IP14167-1 v2
14.4.8.1
Application
M13585-3 v10
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A
(3), DB_BUS_B (3) and DB_LINE (3) functions are used for a line connected to a
double busbar arrangement according to figure 167.
WA1 (A)
WA2 (B)
189
189G
289G
989G
6189
989
289
489G
589G
389G
6289
DB_BUS_B
DB_LINE
DB_BUS_A
en04000518_ansi.vsd
252
152
ANSI04000518 V1 EN-US
Figure 167: Switchyard layout double circuit breaker
Three types of interlocking modules per double circuit breaker bay are defined.
DB_BUS_A (3) handles the circuit breaker QA1 that is connected to busbar WA1 and
the disconnectors and grounding switches of this section. DB_BUS_B (3) handles the
circuit breaker QA2 that is connected to busbar WA2 and the disconnectors and
grounding switches of this section.
M13584-4 v4
For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE and
DB_BUS_B must be used.
14.4.8.2 Configuration setting
M13584-6 v5
For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
Section 14 1MRK 511 401-UUS A
Control
404 Bay control REC670 2.2 ANSI
Application manual

Table of Contents

Other manuals for ABB rec670

Related product manuals