15.1.3.2 Delta blocking scheme
GUID-F4359690-F433-46CB-A173-8C14559E3FCF v1
Set
Operation
=
Enabled
Set
SchemeType
=
DeltaBlocking
Set
tCoord
= 0 s
Set
tSendMin
= 0 s
Set
Unblock
=
Disabled
(Set to
NoRestart
if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart
if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
= 0.035 s
Set
DeltaI
= 10 %IB
Set
DeltaV
= 5 %VB
Set
Delta3I0
= 10 %IB
Set
Delta3V0
= 5 %VB
15.1.3.3 Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
Enabled
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
15.1.3.4 Permissive overreaching scheme
M13869-34 v4
Set
Operation
=
Enabled
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
Set
tSecurity
= 0.035 s
15.1.3.5 Unblocking scheme
M13869-43 v4
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart
if only trip is required)
Set
tSecurity
= 0.035 s
1MRK 511 401-UUS A Section 15
Scheme communication
Bay control REC670 2.2 ANSI 473
Application manual

Table of Contents

Other manuals for ABB rec670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB rec670 and is the answer not in the manual?

ABB rec670 Specifications

General IconGeneral
BrandABB
Modelrec670
CategoryControl Unit
LanguageEnglish

Related product manuals