17.2.3 Setting guidelines
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v2
The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of gas medium supervision i.e.
Off/On.
Pr
esAlmLimit: This is used to set the limit for a pressure alarm condition in the circuit
breaker.
PresLOLimit: This is used to set the limit for a pressure lockout condition in the circuit
breaker.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in the
circuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in the
circuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication, given
in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout indication,
given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set time
delay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set time
delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a set
time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set
time delay in s.
1MRK 511 401-UUS A Section 17
Monitoring
Bay control REC670 2.2 ANSI 523
Application manual

Table of Contents

Other manuals for ABB rec670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB rec670 and is the answer not in the manual?

ABB rec670 Specifications

General IconGeneral
BrandABB
Modelrec670
CategoryControl Unit
LanguageEnglish

Related product manuals