The send signal (CS) might be issued in parallel both from an overreaching zone and
an underreaching, independent tripping zone. The CS signal from the overreaching
zone must not be prolonged while the CS signal from zone 1 can be prolonged.
To secure correct operations of current reversal logic in case of parallel lines the send
signal CS shall not be prolonged. Set the tSendMin to zero in this case.
There is no need to delay the trip at receipt of the signal, so set the timer tCoor
d to
zero.
A B
OR
A
OR
B
OR
A
CS
A
TRIP
B
= OR
B
+ CR
B ,
OR
B
+ T2
IEC09000014-1-en.vsd
IEC09000014 V1 EN-US
Figure 192: Principle of Permissive overreaching scheme
OR: Overreaching
CR: Communication signal received
CS: Communication signal send
T2: Timer step 2
Unblocking scheme
M16866-67 v5
Metallic communication paths adversely af
fected by fault generated noise may not be
suitable for conventional permissive schemes that rely on a signal transmitted during a
protected line fault. W
ith power line carrier for example, the communication signal
may be attenuated by the fault, especially when the fault is close to the line end,
thereby disabling the communication channel.
To overcome the lower dependability in permissive schemes, an unblocking function
can be used. Use this function at older, less reliable, power-line carrier (PLC)
communication, where the signal has to be sent through the primary fault. The
unblocking function uses a guard signal CR_GUARD, which must always be present,
even when no CR signal is received. The absence of the CR_GUARD signal during the
security time is used as a CR signal. This also enables a permissive scheme to operate
when the line fault blocks the signal transmission. Set the tSecurity to 35 ms.
1MRK 511 401-UUS A Section 15
Scheme communication
Bay control REC670 2.2 ANSI 471
Application manual

Table of Contents

Other manuals for ABB rec670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB rec670 and is the answer not in the manual?

ABB rec670 Specifications

General IconGeneral
BrandABB
Modelrec670
CategoryControl Unit
LanguageEnglish

Related product manuals