HMI is Main menu/Configuration
/Time/Synchronization. The parameters are
categorized as Time Synchronization (TIMESYNCHGEN) and IRIG-B settings (IRIG-
B:1) in case that IRIG-B is used as the external time synchronization source.
TimeSynch
M11348-167 v15
When the source of the time synchronization is selected on the local HMI, the
parameter is called TimeSynch. The time synchronization source can also be set from
PCM600. The setting alternatives are:
FineSyncSource which can have the following values:
Disabled
SPA
LON
BIN (Binary Minute Pulse)
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
CoarseSyncSrc which can have the following values:
Disabled
SPA
LON
DNP
IEC 60870-5-103
The function input to be used for minute-pulse synchronization is called BININPUT.
For a description of the BININPUT settings, see the Technical Manual.
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
The parameter SyncMaster defines if the IED is a master, or not a master for time
synchronization within a Substation Automation System, for IEDs connected in a
communication network (IEC 61850-8-1). The SyncMaster can have the following
values:
Section 23 1MRK 511 401-UUS A
Basic IED functions
624 Bay control REC670 2.2 ANSI
Application manual