6.1.1.2 Monitoring an internal relay fault
The flashing green LED indicates an internal relay fault. Internal relay fault
messages are shown in a dialog box. Only one dialog box can be shown at a time,
therefore the relay has internal priority for indication messages and tripping data.
Internal fault has always higher priority than a warning.
See the troubleshooting section for more details.
Internal Fault
Test
Code 00. 01. 08. 008. 19
20. 01. 2021
22: 20: 34. 690
GUID-3C2CEBF9-8D06-4D1F-AF38-50A7E3E330F9 V1 EN-US
Figure 26: Fault indication
1. Select Main menu/Monitoring/IED status/Self-supervision to monitor the
latest fault indication.
2.
Press or to scroll the view.
6.1.1.3 Monitoring condition monitoring data
1. Select Main menu/Monitoring/I/O status/Condition monitoring.
2.
Press or to scroll the view.
3.
Press
to enter or to exit a submenu.
With PCM600 the user can map output signals from condition monitoring related
function blocks to the appropriate destinations.
6.1.2 Measured and calculated values
Measurement view in Main Menu/Measurements shows the momentary actual
values for various power system measurements.
All values show the momentary measurement value.
Invalid or questionable measurement values are presented in
parentheses.
Section 6 2NGA000823 A
Operating procedures
44 REX610