8.4.3.3 Changing display symbols
Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and
IEC-ANSI.
1. Select Main Menu/Configuration/HMI/FB naming convention and press
.
2.
Change the display symbols with or .
3.
Press
to confirm the selection.
HMI
FB naming convention
=IEC61850
Default view
=Main menu
A
GUID-12F588B9-1A97-4C98-B0C9-3F88F1652EC2 V1 EN-US
Figure 52: Changing the function block naming convention
The change in LHMI display symbols takes effect immediately
without the need to reboot the protection relay.
8.4.3.4 Changing default view
The default view of the display is Main menu unless set otherwise.
1.
Select Main menu/Configuration/HMI/Default view and press
.
HMI
FB naming convention
=IEC61850
Default view
=Main menu
A
GUID-50803036-A89C-4532-AE5B-A0F648A3FF1A V1 EN-US
Figure 53: Changing the default view
2.
Change the default view with or .
3.
Press to confirm the selection.
Section 8 2NGA000823 A
Commissioning
76 REX610
Operation Manual