Information
Closing in
17 s
Press any button to
cancel close
GUID-71923E01-5CE4-48C2-A67A-774512902C47 V1 EN-US
Figure 35: Delay view
The display backlight stays on for the delay also if the backlight
timeout is shorter than the closing delay.
6.3 Resetting protection relay
6.3.1 Clearing and acknowledging via the local HMI
All messages and indications, including LEDs and latched outputs as well as
registers and indications, including recordings can be reset, acknowledged or
cleared with the Clear button. Pressing the Clear button activates a menu for
selecting the wanted clearing or reset function. Events and alarms assigned to
programmable LEDs can also be cleared with the Clear button.
1.
Press
to activate the Clear view.
All the items that can be cleared are shown.
Indications and LEDs
Programmable LEDs
Events
Disturbance records
Acc. energy of circuit breaker condition monitoring
Rem. life of circuit breaker condition monitoring
Travel times of circuit breaker condition monitoring
Spr. charge time of circuit breaker condition monitoring
Temperature of three-phase thermal protection for feeders, cables and
distribution transformer
Reset of autoreclosing
Counters for autoreclosing
Master trip
Section 6 2NGA000823 A
Operating procedures
50 REX610
Operation Manual