Parameter or counter Description
Parity errors Counts the number of parity errors detected in
characters received
Overrun errors Counts the number of overrun errors detected in
characters received
Framing errors Counts the number of framing errors detected in
characters received
Reset counter Resets all counters to zero
8.4.2.3 Defining Ethernet port settings
Change the Ethernet port settings primarily via PCM600 to ensure
that PCM600 is able to export a consistent configuration to
SYS600. Ethernet port settings are recommended to be changed
only when the device is stand-alone and properly configured.
1. Select Main menu/Configuration/Communication/Ethernet/Rear port.
2. Define the settings for the Ethernet port.
• IP address
• Subnet mask
• Default gateway of the optional rear port Ethernet connector
8.4.2.4 Defining serial port settings
1. Select Main menu/Configuration/Communication/COM1.
2. Define the settings for the serial port.
It is possible to change the general serial communication parameters per port.
Select fiber or galvanic mode with the proper baud rate, parity and delays
depending on the system architecture and the selected physical
communication port.
COM1
Serial mode
=RS485 2Wire
Baudrate
=9600
A
GUID-EA1FA1A1-5067-4719-A351-DBF3D5847E1D V1 EN-US
Figure 50: Defining the serial port settings
Section 8 2NGA000823 A
Commissioning
74 REX610
Operation Manual