Indications and LEDs
=Cancel
Programmable LEDs
=Cancel
A
GUID-EF12B88F-0EC7-4429-8587-984B1E85A317 V1 EN-US
Figure 36: Clear view
2.
Select the item to be cleared with or .
3.
Press , change the value with or and press again.
The item is now cleared.
4. Repeat the steps to clear other items.
Use the button as a shortcut for clearing. A three-second press
clears trip LEDs and a six-second press clears the programmable
LEDs.
6.4 Changing protection relay functionality
6.4.1 Defining the setting group
6.4.1.1 Activating a setting group
Protection relay settings are planned in advance for different operation conditions
by calculating setting values to different setting groups. The active setting group
can be changed by the protection relay application or manually from the menu.
1.
Select Main menu/Settings/Setting group/Active group and press
.
Setting group
Active group
=1
Copy group 1
=Cancel
A!
GUID-ACD694E0-3223-4ABE-BD86-10A2A8543E10 V1 EN-US
Figure 37: Active setting group
2.
Select the setting group with or .
3.
Press to confirm the selection or to cancel.
2NGA000823 A Section 6
Operating procedures
REX610 51
Operation Manual