6.1.2.1 Measured values
Measured values can be accessed through the LHMI.
Table 16: Examples of the measured values
Indicator
Description
IL1-A Current measured on phase L1
IL2-A Current measured on phase L2
IL3-A Current measured on phase L3
I
0
-A
Measured earth-fault current
U
0
-kV
Measured residual voltage
U12-kV Measured phase-to-phase voltage U12
U23-kV Measured phase-to-phase voltage U23
U31-kV Measured phase-to-phase voltage U31
NgSeq-A Negative-phase-sequence current
Ps-Seq-A Positive-phase-sequence current
Zr-Seq-A Zero-phase-sequence current
6.1.2.2 Using local HMI for monitoring
1. Select Main menu/Measurements to monitor measured and calculated
values.
The list of protection relay's basic measurements is shown.
2.
Scroll the view with
and .
6.1.3 Recorded data
The protection relay is provided with intelligent and flexible functionality that
collects different kinds of data. The recorded data gives substantial information for
post fault analysis.
• Disturbance records
• Events
6.1.3.1 Creating disturbance recordings
Normally disturbance recordings are triggered by the protection relay applications
but the recording can also be triggered manually.
1. Select Main menu/Disturbance records.
2.
Select Trig recording with
or .
3.
Press , change the value with or and press again.
2NGA000823 A Section 6
Operating procedures
REX610 45
Operation Manual