IED test ! A
Internal fault test
=Test o
Remote test mode
=O
GUID-2CD3E04A-EACA-456E-8315-B8FE0C69F1AE V1 EN-US
Figure 63: Entering IED blocked or IED test and blocked mode
2.
Select the test mode status with or . Press to confirm the selection.
If the IED blocked or IED test and blocked mode is not cancelled, it
remains on and the Start and/or Ready LEDs remain flashing.
8.6 ABB Product Data Registration
The ABB Product Data Registration feature traces composition changes in the
protection relay's SW or HW. Traceability allows better support and maintenance
possibilities.
The PCM600 reads the changed data from the protection relay. Therefore a
connection to the protection relay must be established first. Composition data can
be read with PCM600 by enabling LCT during PCM600 installation and activating
collection in PCM600 from 'Lifecycle Handling' menu. For detailed information
see PCM600 online help.
The number of composition changes can be seen from the Composition changes
parameter in Main Menu/Monitoring/IED status. Composition changes
increment for firmware updates and site information changes.
2NGA000823 A Section 8
Commissioning
REX610 85
Operation Manual