[1]=
↦
+_ _ _ _ 20 ms
[2]=20 ms
[3]=20 ms
[4]=20 ms
A!
SG1: Operate delay ...
GUID-7EC94852-A954-4A02-91DB-73BAE78A5C7E V1 EN-US
Figure 58: Editing the setting group value
The active setting group is indicated with an asterisk * .
Switching the Operation parameter of a function block on or off
restarts all control and protection functions.
Activating a setting group
Protection relay settings are planned in advance for different operation conditions
by calculating setting values to different setting groups. The active setting group
can be changed by the protection relay application or manually from the menu.
1.
Select Main menu/Settings/Setting group/Active group and press .
Setting group
Active group
=1
Copy group 1
=Cancel
A!
GUID-ACD694E0-3223-4ABE-BD86-10A2A8543E10 V1 EN-US
Figure 59: Active setting group
2.
Select the setting group with or .
3.
Press to confirm the selection or to cancel.
Setting group
Active group
=
↦
+_1
Copy group 1
=Cancel
A!
GUID-2C0AF084-F604-45E3-B7C8-7A152B31950C V1 EN-US
Figure 60: Selecting the active setting group
4. Commit the settings.
Section 8 2NGA000823 A
Commissioning
80 REX610
Operation Manual