Figure 7-9: Low value current reading verification
16. Keep the default target low value of 0 (Figure 7-10
) or type an appropriate value for your
scenario. This example uses 0 for a 0-1500 PSI measurement range. A voltage value of 1 Vdc
represents 0 PSI.
Figure 7-10: Default low calibration value for measurement range
17. Click OK. The Reading column updates to reflect the signal value associated with the low value
of the range (Figure 7-11
).