134 | RMC-100| 2105552MNAE
Figure 7-11: Low calibration value reading
18. Adjust the calibrator to apply the high value (100%) of the signal range. For example, if the
signal range of the external device is 1-5 Vdc, apply 5 Vdc.
19. Click 100% Cal Point. The Enter 100% Calibration Value dialog box displays (Figure 7-12
).
20. Observe the value in the Current Reading field. When it stabilizes this value should match or be
close to the signal value from the calibrator (~ 5 Vdc).
21. Type the high range value in the field (1500 for this example) and click OK.
Figure 7-12: User-defined high value
The Reading column updates to reflect the signal value associated with the high value of the range
(Figure 7-13
).

Table of Contents