67
48 TB13B (TB-13B INPUT FUNCTION)
This parameter is used to select the function of terminal TB-13B. Closing TB-
13B to TB-2 activates the TB - 13B function. The following functions can be
selected:
NONE Disables the TB-13B function.
0-10VDC Selects 0-10 VDC as the AUTO speed reference input. The
0-10 VDC signal is wired to TB-5A and TB-2.
4-20 MA Selects 4-20 mA as the AUTO speed reference input. The 4-
20 mA signal is wired to TB-5B and TB-2.
SPEED#2 Selects PRESET SPEED #2 as the AUTO speed reference.
INC FREQ Increase frequency setpoint. Used with the MOP (motor
operated pot) function. Refer to Section 14.2.6 - SPEED
REFERENCE SELECTION.
JOG FWD Jog in the forward direction. Active only when drive is
STOPPED. The jog speed is set by Parameter 2 -SPEED#2.
JOG REV Jog in the reverse direction. Active only when drive is
STOPPED. The jog speed is set by Parameter 2 - SPEED#2.
49 TB13C (TB-13C INPUT FUNCTION)
This parameter is used to select the function of terminal TB-13C. Closing TB-
13C to TB-2 activates the TB - 13C input function. The following functions can
be selected:
NONE Disables the TB-13C function.
WARNING!
When operating in JOG mode, the STOP key WILL NOT stop the drive. To stop
the drive, the contact between TB-13B and TB-2 must be opened.
WARNING!
If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT
be used as a STOP switch! This is true in LOCAL and REMOTE mode. Incorrect
use of TB-1 may result in damage to equipment and/or injury to personnel!