68
0-10VDC Selects 0-10 VDC as the AUTO speed reference input. The
0-10 VDC signal is wired to TB-5A and TB-2.
4-20 MA Selects 4-20 mA as the AUTO speed reference input. The 4-
20 mA signal is wired to TB-5B and TB-2.
SPEED#3 Selects PRESET SPEED #3 as the AUTO speed reference.
LOC SEL LOCAL SELECT - Selects LOCAL mode when Parameter 30
- CONTROL is set to BOTH. Drive is in REMOTE mode if
contact closure is not made.
RUN REV RUN REVERSE - Run in reverse direction. Requires a
maintained contact closure - close to RUN in reverse direction,
open to STOP. This will cause TB-12A to function as RUN
FORWARD, also requiring a maintained contact to RUN in
forward.
STRT REV START REVERSE - Start in reverse direction. Requires a
momentary contact closure to RUN in reverse direction. A
momentary STOP contact must be wired between TB-1 and
TB-2. Setting this parameter to START REVERSE causes
TB-12A to function as START FORWARD, also requiring a
momentary contact closure to RUN in forward.
50 TB13D (TB-13D FUNCTION)
This parameter selects the function for TB-13D.
EXT FAULT Sets TB-13D as a normally open EXTERNAL FAULT
contact. Close TB-13D to TB-2 to trip the drive into an
EXTERNAL FAULT.
EXT / FAULT Sets TB-13D as a normally closed EXTERNAL FAULT
contact. Open TB-13D to TB-2 to trip the drive into an
EXTERNAL FAULT.
EXT CLEAR Sets TB-13D as a normally open FAULT RESET. Close TB-
13D to TB-2 to clear a fault.
WARNING!
STOP (TB-1) and EXTERNAL FAULT (TB-13D) circuitry may be disabled if
parameters are reset to factory defaults! The drive must be reprogrammed after a
RESET in order to insure proper operation (see Parameter 65 - PROGRAM).
FAILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT AND/
OR INJURY TO PERSONNEL!