IST Series UPS (10kVA-200kVA)
User Manual 6 Maintenance and Troubleshooting
81
6 Maintenance and Troubleshooting
6.1 Maintenance Guide
Proper maintenance is the key to make the device operate in the best status and with a longer
service life.
6.1.1 Safety Precautions
To ensure human safety and equipment security, observe the following precautions.
Please keep in mind that there is dangerous voltage inside the UPS even if the UPS
does not operate. Before maintenance, use a multi-meter to check the voltage and make
sure that the UPS is completely shut down and stays in safe status.
Before close the battery breaker at any time, use a multi-meter to measure if the voltage
of multi-meter is normal and the polarity is reverse connected. If the result is abnormal, it
is strictly forbidden to close the battery breaker.
Do not wear any conductive metal objects during operation, such as ring, watch.
Observe safety regulations strictly. If any doubt, consult professionals.
6.1.2 Preventive Maintenance
To improve the UPS reliability and efficacy, perform the following maintenance tasks on a
quarterly basis.
Keep the operating environment free from dust and chemical pollutants.
Check if the wiring terminals on input, output cables are in good contact every half year.
Check the fans work status periodically and avoid blocking the air vents. If a fan is
damaged, maintain or replace it in time.
Check the voltage of batteries periodically and ensure that the battery voltage is within
the normal range.
Check the UPS status periodically and ensure that any fault can be found in time.
6.2 Battery Maintenance
Battery charge requirements