AERMEC Multichiller-Evo - Installer - Thresholds & Timings: Chiller Ignition Priority; Backup Chiller Settings

AERMEC Multichiller-Evo
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
INSTALLER - Thresholds and ming - Chiller ignion Priority/Order sengs for xed threshold management
A
B
D

Index Meaning
1
Indicates the priority index assigned to the chiller (n) both cooling and heating; the lower the index
the higher the chiller priority during ignition; if two or more chillers have the same priority index, the
one with the least number of worked hours will have priority (in order to balance them); the logic
is reversed during switch-o, starting to switch-o the chiller with the higher index (if more chillers
have the same index, the one with the highest number of worked hours will switch-o rst);
ACTIONS
AVAILABLE:
A C D



E
F
B
C


INSTALLER - Thresholds and ming - Backup chiller sengs
A
B
D

Index Meaning
1
Indicates the possible chiller used as backup; if one of the system chillers is indicated as backup, said
chiller will always be o, automatically activating it if another chiller is locked by a serious alarm;
ACTIONS
AVAILABLE:
A C
D


B
C

1
1
1
E F E F