14 INPUT/OUTPUT MENU
This menu is used to display the state of the inputs and outputs, both digital as well
as analogue.
The rst mask, which is present only in the master card parameters, summarises
the machine status with a graphic indication of the compressor power (no. capacity
controls), input temperature, master water output and circuit operating status.
12.5 000 %
12.0
%
%
%
2
3
4
al
In
Out
This mask displays:
1. In: water inlet temperature (master)
2. Out: water outlet temperature (master)
3. Cooling capacity of the compressors present from 1 to 4, expressed as a
percentage
4. Status indication of circuits from 1 to 4:
— ok: operative
— al: stopped due to alarm
— ---: No present
— sp: safety reducer
— WW: wait for safety dierential
— PD: wait for PullDown
14.1 DIGITAL INPUT/OUTPUT GENERAL MONITOR
CCC000C00000CC000C
1
0000000C0000000000
Digital outputs
— Digital input state: starting from the left to the right, they are ID1 - ID18 (O =
open; C = closed)
— Digital output state: starting from the left to the right, they are C1 - C18 (O =
open; C = closed)
14.2 TRANSDUCER HIGH AND LOW PRESSURE MONITOR
(U1):
(U2):
13.5 bar
03.0 bar
HP
LP
— H.P. (U1): high pressure transducer reading
— L.P. (U2): low pressure transducer reading
14.3 TIA, TUAC AND TGP PROBE VALUES MONITOR
(U3):
(U4):
12.5 °C
074.0 °C
TIA
TGP
— TIA (U3): evaporator water inlet temperature probe reading (master only)
— TUAC (U3): common water inlet temperature probe reading (in case of adjust-
ment at the outlet with multiple parallel connected evaporators) (slave 1 only)
— TGP (U4): discharge gas temperature probe reading
14.4 TRANSFORMER INLET AND EVAPORATOR WATER
OUTLET TEMPERATURE MONITOR
(U5):
(U6):
012.0 °C
000.0 A
TUA
T.A.
— TUA (U5): evaporator water outlet temperature probe reading
— T.A. (U6): Ammetric transformer input (A)
14.5 EVAPORATOR INLET GAS TEMPERATURE AND
MULTIFUNCTION INPUT MONITOR
(U7):
(U8):
---- °C
---- °C
MULTI
TEV
— MULTI (U7): Multifunction input (master only)
— TEV (U8): evaporator input gas temperature probe reading