Chapter 1
Process Control Instructions
156 Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
CV1ROCPosLimit REAL CV1 rate of change limit, in percent
per second. Rate of change limiting is
only used when in Auto mode or in
Manual mode if CVManLimiting is
TRUE. A value of zero disables CV1 ROC
limiting. If value of CV1ROCLimit < 0,
set bit in Status and disable CV1 ROC
limiting.
Valid = 0.0 to maximum positive float
Default = 0.0
CV2ROCPosLimit REAL CV2 rate of change limit, in percent
per second. Rate of change limiting is
only used when in Auto mode or in
Manual mode if CVManLimiting is
TRUE. A value of zero disables CV2 ROC
limiting. If value of CV2ROCLimit < 0,
set bit in Status and disable CV2 ROC
limiting.
Valid = 0.0 to maximum positive float
Default = 0.0
CV3ROCPosLimit REAL CV3 rate of change limit, in percent
per second. Rate of change limiting is
only used when in Auto mode or in
Manual mode if CVManLimiting is
TRUE. A value of zero disables CV3 ROC
limiting. If value of CV3ROCLimit < 0,
set bit in Status and disable CV3 ROC
limiting.
Valid = 0.0 to maximum positive float
Default = 0.0
CV1ROCNegLimit REAL CV1 rate of change limit, in percent
per second. Rate of change limiting is
only used when in Auto mode or in
Manual mode if CVManLimiting is
TRUE. A value of zero disables CV1 ROC
limiting. If value of CV1ROCLimit < 0,
set bit in Status and disable CV1 ROC
limiting.
Valid = 0.0 to maximum positive float
Default = 0.0
CV2ROCNegLimit REAL CV2 rate of change limit, in percent
per second. Rate of change limiting is
only used when in Auto mode or in
Manual mode if CVManLimiting is
TRUE. A value of zero disables CV2 ROC
limiting. If value of CV2ROCLimit < 0,
set bit in Status and disable CV2 ROC
limiting.
Valid = 0.0 to maximum positive float
Default = 0.0
CV3ROCNegLimit REAL CV3 rate of change limit, in percent
per second. Rate of change limiting is
only used when in Auto mode or in
Manual mode if CVManLimiting is
TRUE. A value of zero disables CV3 ROC
limiting. If value of CV3ROCLimit < 0,
set bit in Status and disable CV3 ROC
limiting.
Valid = 0.0 to maximum positive float
Default = 0.0

Table of Contents

Other manuals for Allen-Bradley LOGIX 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley LOGIX 5000 and is the answer not in the manual?

Allen-Bradley LOGIX 5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelLOGIX 5000
CategoryController
LanguageEnglish

Related product manuals