Process Control Instructions
162 Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
ProgCV1HandReq BOOL Program-Hand mode request for CV1.
Set TRUE by the user program to
request Hand mode. This value will
usually be read as a digital input from
a hand/auto station.
Default = FALSE
ProgCV2HandReq BOOL Program-Hand mode request for CV2.
Set TRUE by the user program to
request Hand mode. This value will
usually be read as a digital input from
a hand/auto station.
Default = FALSE
ProgCV3HandReq BOOL Program-Hand mode request for CV3.
Set TRUE by the user program to
request Hand mode. This value will
usually be read as a digital input from
a hand/auto station.
Default = FALSE
OperProgReq BOOL Operator Program Request.
Set TRUE by the operator interface to
request Program control. The function
block resets this parameter to FALSE.
Default = FALSE
OperOperReq BOOL Operator Operator Request.
Set TRUE by the operator interface to
request Operator control. The function
block will reset this parameter to
FALSE.
Default = FALSE
OperCV1AutoReq BOOL Operator-Auto mode request for CV1.
Set TRUE by the operator interface to
request Auto mode. The function
block will reset this parameter to
FALSE.
Default = FALSE
OperCV2AutoReq BOOL Operator-Auto mode request for CV2.
Set TRUE by the operator interface to
request Auto mode. The function
block will reset this parameter to
FALSE.
Default = FALSE
OperCV3AutoReq BOOL Operator-Auto mode request for CV3.
Set TRUE by the operator interface to
request Auto mode. The function
block will reset this parameter to
FALSE.
Default = FALSE
OperCV1ManualReq BOOL Operator-Manual mode request for
CV1.
Set TRUE by the operator interface to
request Manual mode. The function
block resets this parameter to FALSE.
Default = FALSE
OperCV2ManualReq BOOL Operator-Manual mode request for
CV2.
Set TRUE by the operator interface to
request Manual mode. The function
block resets this parameter to FALSE.
Default = FALSE