Process Control Instructions
Chapter 1
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018 191
ProgProgReq BOOL Program Program Request.
Set TRUE by the user program to request
Program control. Ignored if ProgOperReq is
TRUE. Holding this TRUE and ProgOperReq
FALSE can be used to lock the function
block into program control.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgOperReq BOOL Program Operator Request. Set TRUE by the
user program to request Operator control.
Holding this TRUE can be used to lock the
function block into operator control. When
ProgValueReset is TRUE, the function block
resets the input to FALSE.
Default = FALSE
ProgCasRatReq BOOL Program-Cascade/Ratio mode request. Set
TRUE by the user program to request
Cascasde/Ratio mode. When
ProgValueReset is TRUE, the function block
resets the input to FALSE.
Default = FALSE
ProgAutoReq BOOL Program-Auto mode request. Set TRUE by
the user program to request Auto mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgManualReq BOOL Program-Manual mode request. Set TRUE
by the user program to request Manual
mode. When ProgValueReset is TRUE, the
function block resets the input to FALSE.
Default = FALSE
ProgOverrideReq BOOL Program-Override mode request. Set TRUE
by the user program to request Override
mode. When ProgValueReset is TRUE, the
function block resets the input to FALSE.
Default = FALSE
ProgHandReq BOOL Program-Hand mode request. Set TRUE by
the user program to request Hand mode.
This value will usually be read as a digital
input from a hand/auto station. When
ProgValueReset is TRUE, the function block
resets the input to FALSE.
Default = FALSE
OperProgReq BOOL Operator Program Request. Set TRUE by the
operator interface to request Program
control. The function block resets this
parameter to FALSE.
Default = FALSE
OperOperReq
Operator Operator Request. Set TRUE by
the operator interface to request Operator
control. The function block will reset this
parameter to FALSE.
Default = FALSE
OperCasRatReq BOOL Operator-CascadeRatio mode request. Set
TRUE by the operator interface to request
CascadeRatio mode. The function block will
reset this parameter to FALSE.
Default = FALSE
OperAutoReq BOOL Operator-Auto mode request. Set TRUE by
the operator interface to request Auto
mode. The function block will reset this
parameter to FALSE.
Default = FALSE

Table of Contents

Other manuals for Allen-Bradley LOGIX 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley LOGIX 5000 and is the answer not in the manual?

Allen-Bradley LOGIX 5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelLOGIX 5000
CategoryController
LanguageEnglish

Related product manuals