Process Control Instructions
222 Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Input Parameters Data
Type
Description Values
CV1PV2ModelInit BOOL Internal model initialization switch for CV1 - PV2.
Refer to Function Block Attributes.
Default = FALSE
CV2PV2ModelInit BOOL Internal model initialization switch for CV2 - PV2.
Refer to Function Block Attributes.
Default = FALSE
CV3PV2ModelInit BOOL Internal model initialization switch for CV3 - PV2.
Refer to Function Block Attributes.
Default = FALSE
PV1Factor REAL Non-integrating model approximation factor for
PV1. Only used for integrating process types.
Default = 100
PV2Factor
Non-integrating model approximation factor for
PV2. Only used for integrating process types.
Default = 100
AtuneCV1Start BOOL Start Autotune request for CV1. Set True to
initiate auto tuning of the CV1 output for both
PV1 and PV2. Ignored when CV1 is not in Manual
mode. The function block resets the input to
FALSE.
Default = FALSE
AtuneCV2Start BOOL Start Autotune request for CV2. Set True to
initiate auto tuning of the CV2 output for both
PV1 and PV2. Ignored when CV2 is not in Manual
mode. The function block resets the input to
FALSE.
Default = FALSE
AtuneCV3Start BOOL Start Autotune request for CV3. Set True to
initiate auto tuning of the CV3 output for both
PV1 and PV2. Ignored when CV3 is not in Manual
mode. The function block resets the input to
FALSE.
Default = FALSE
AtuneCV1PV1UseM
odel
BOOL Use Autotune model request for CV1 - PV1. Set
True to replace the current model parameters
with the calculated Autotune model parameters.
The function block resets the input parameter to
FALSE.
Default = FALSE
AtuneCV2PV1UseM
odel
BOOL Use Autotune model request for CV2 - PV1. Set
True to replace the current model parameters
with the calculated Autotune model parameters.
The function block resets the input parameter to
FALSE.
Default = FALSE
AtuneCV3PV1UseM
odel
BOOL Use Autotune model request for CV3 - PV1. Set
True to replace the current model parameters
with the calculated Autotune model parameters.
The function block resets the input parameter to
FALSE.
Default = FALSE
AtuneCV1PV2UseM
odel
BOOL Use Autotune model request for CV1 - PV2. Set
True to replace the current model parameters
with the calculated Autotune model parameters.
The function block resets the input parameter to
FALSE.
Default = FALSE
AtuneCV2PV2UseM
odel
BOOL Use Autotune model request for CV2 - PV2. Set
True to replace the current model parameters
with the calculated Autotune model parameters.
The function block resets the input parameter to
FALSE.
Default = FALSE