EasyManua.ls Logo

Allen-Bradley LOGIX 5000

Allen-Bradley LOGIX 5000
561 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1
Process Control Instructions
24 Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Rate-of-change Alarm
The rate-of-change (ROC) alarm compares the change of the input over the
ROCPeriod to the rate-of-change limits. The ROCPeriod provides a type of
deadband for the rate-of-change alarm. For example, define an ROC alarm limit of
2
O
F/second with a period of execution of 100 ms. If you use an analog input
module with a resolution of 1
O
F, every time the input value changes, an ROC
alarm is generated because the instruction calculates an effective rate of
10°F/second. However, enter an ROCPeriod of 1 sec and the instruction only
generates an alarm if the rate truly exceeds the 2
O
F/second limit.
The ROC alarm calculates the rate-of-change as:
The instruction performs this calculation when the ROCPeriod expires. Once the
instruction calculates the ROC, it determines alarms as:
Monitoring the ALM Instruction
There is an operator faceplate available for the ALM instruction.
Affects Math Status Flags
No
Major/Minor Faults
None specific to this instruction. See Common Attributes for operand-related
faults.

Table of Contents

Other manuals for Allen-Bradley LOGIX 5000

Related product manuals