FORM DOC 120 A
MU 7033 EN M
FLEXICOMPT AUTONOME+
Page 9/42
This document is available on www.alma-alma.fr
4.1 Mobile installation
The vacuum between the connecting device and stripping valve on the FLEXICOMPT
AUTONOME+ device must be rigid with a 15 degree angle, an 80mm minimum diameter and
a length of less than 80mm.
4.2 FLEXICOMPT AUTONOME+ AdBlue
The FLEXICOMPT AUTONOME+ AdBlue must be rinsed with water after use in order to clean
it and to ensure it works properly.
5 IGNITION AND OPERATION
The FLEXICOMPT AUTONOME+ measuring system operates with an empty hose. The operator
connects it to the API adaptor and then connects the hose to the FLEXICOMPT AUTONOME+
outlet.
The operating procedure is as follows:
Reset the volume on the UNI-2. The operator opens the tank valve. The metering starts as
soon as the UNI-2 records impulses coming from the turbine. The metered volume is
continually displayed on the UNI-2.
For partial emptying:
The operator stops metering by closing the tank valve. The metering stops when the UNI-2
notes that both gas detectors are wet and flow rate is to zero.
For complete emptying:
The operating procedure is identical to the partial emptying procedure but there is no voluntary
action on the tank valve.