3-18 | Thermox TM 2000 Oxygen Analyzer
Any terminals not described in this section are reserved for future
use.
This wiring section shows you how to make the following connections:
• ACmainssupplytocontrolunit
• ACmainssupplytosensor
• Controlunittosensor
• Controlunittocurrentoutputdevices
• Controlunittoalarmdevices
• Controlunittoremotecalibrationunit
• Controlunittohostcomputer(RS-485communications)
This wiring section also provides mandatory grounding and shielding
requirements.
General Wiring and Conduit Requirements
This section describes general wiring and conduit requirements:
• Sensorwiringconductorsmustberatedataminimumof80°C.All
other wiring conductor ratings should be for the minimum tempera-
ture required for the equipment being connected to the analyzer, but
not less than 60° C.
• Followallapplicableelectricalcodesforyourlocation.
• UseonlytheapplicableNEMA-approvedconduitfittingsorcable
fittings to maintain the NEMA rating for the Series 2000 controller
or sensor enclosure. If not using a conduit entry, leave the factory
NEMA-approved plugs intact. Never leave any holes unplugged.
• ForACmainssupplywiring,usebetween12and14AmericanWire
Gauge (AWG). For all signal wiring, other than to the sensor, use 18 to
22 AWG. For sensor connections, Figure 3-17 shows the recommended
sensor cabling.
• Usetwistedpaircableinrigidmetalconduitorinanoverallbraided
shield for all wires other than AC mains supply.