MAN 2326-13
42
10. For Smoke detecon sampling systems, perform the following
i
Measure the response me of all sampling points using
smoke placed at each sampling point.
ii
Check the back-up power supply capacity.
iii
Check the operaon of alarm sengs and indicators.
iv
Check operaon of remote indicaon of alarm and fault
signals.
v
Check the operaon of airow failure indicators.
vi
Check the operaon of the system (signal) failure indicators.
vii
Check the isolate/reset funcons.
viii
Check the fault and alarm test facilies.
11. Test each ancillary funcon by operang the alarm zone facility(ies), associated with the ancillary
funcon.
Yes No N/A
12. Alarm Signalling
i
Check that the master alarm facility is able to receive the
alarm signal by operang each alarm zone facility.
ii
Check that the master alarm facility iniates an alarm to the
re control staon equipment.
13. Baery Supply
i
Check that both the primary and secondary power sources
are of a suitable type and capacity.
ii
Perform a oat voltage check according to the baery
manufacturer's recommendaon to ensure that the charger
type and seng is correct.
Type of baery.
Float voltage/ required.
Charger type.
Charger set at.
14.
Check that all alarm zone facilies have been correctly labelled and
that the alarm zone is immediately apparent from the labelling.
15.
Check the 'as-installed' drawings are marked up, are consistent with
the installaon and the operator's manual is relevant to the
installaon.
16.
Ensure the results of these tests are recorded in the system logbook.