Arkel ArLine User Manual V1.24
25. Remote Update
Software update of Arkel ArLine devices is provided over the internet. The hardware software of Arkel ArLine-M, Arkel ArLine-
S-COP, Arkel ArLine-S-TP and Arkel ArLine-S-INT can be updated via the internet. When a new software version is released
by ARKEL, it can be updated in two ways:
• When the new software version is released by ARKEL, all Arkel ArLine systems with internet connection are
automatically updated between 02:00 and 03:00 hours. This update method does not require user intervention. When
the device powered up for the first time, the update is made at the specified times of the same day.
• If you don’t want to wait for the update, before the device is turned off. If the device continues to operate from the
battery, it turned off with button on the Arkel ArLine-M. While the device energizing again with 24V, press the button
on the Arkel ArLine-M simultaneously for 5 to 10 seconds. In this case, the device switches to update mode and the
update process starts. While the device energizing. When the device powered up for the first time, this is also possible.
The following conditions must be met for device update:
• SIM card must be inserted and there should be uninterrupted connection.
• It is not necessary to supply via 24V. When the device supplied from battery, it doesn’t update.
Software update takes between 15-30min.
‼ Warning: In case of the device update, if the supply and battery are interrupted, the firmware will be damaged and the
firmware don’t use.
26. Inspection and testing before the lift are taken into service (EN 81-28:2018, 6.3)
26.1. Alarm
1. Press the alarm button in the car for more than 30 seconds. The alarm starts.
2. Check the response of the rescue service/personnel.
26.2. End of Alarm
1. After performing the alarm test in item 21.1, terminate the alarm in one of the following ways:
2. Press and hold the button on the Arkel ArLine-M device for 3 seconds.
3. By activating an input to which the "EOA - Alarm end" function is assigned on the Arkel ArLine-M device or,
4. With the alarm termination tool on ARKEL Cloud menu.
5. Check that the yellow pictogram LED is turned off.
26.3. Emergency Electric Power Supply
1. Disconnect the 24V supply (100-1000) of the Arkel ArLine-M device. The device will continue to operate from the
battery.
2. Check the alarm in accordance with 21.1.
3. Reconnect the 24V supply of the Arkel ArLine-M device.
4. Disconnect the battery supply.
5. Open the Arkel ArLine-M box and remove the battery connector on the pcb.
6. Check for a battery failure:
7. Check that the BAT LED on the Arkel ArLine-M is lit.
8. Check the ARKEL Cloud screen for a battery alarm.
9. Check that a battery alarm SMS message is sent to the phone number entered for the technical alarm.
10. If used, check that the Arkel ArLine-M programmable relay function 'BATF - Battery alarm' is active.
11. Reconnect the battery supply.
Reconnect the battery connector on the Arkel ArLine-M pcb and close the box.
26.4. Information in the lift car
During the test in article 21.1, verify the yellow-green pictograms, audible signals and voice communication.
26.5. Communication
1 Press the alarm button for 3 seconds when the car and landing doors are not fully open in the lift.
2 The alarm starts.
3 Check answer.
4 Ask the rescue service/staff to turn off the voice communication.
5 Restart the alarm and check the response before terminating the alarm.