- 19 -
2.4.5 Sockets panel
X22 .....Female socket 63A 4P
X23 .....Female socket 32A 4P
X21 .....Female socket 125A 4P
X3 ....... Socket 16A 1P+N male (optional in
ZBE)
X24 .....Female socket 16A 2P
X25 .....Female socket 16A 2P
X2 ....... Socket 125A 3P+N male
The ESS is provided with inlet and outlets sockets:
– One main inlet 3-phases socket X2 to connect to
the external power supply (genset or mains).
– Several 3-phases (X21-22-23) and 2 single phase
outlet sockets (X24-25) to connect the different
loads to the ESS.
– One single phase inlet socket X3 (optional in
ZBE) to connect the ESS to an external supply in
order to slowly recharge the ESS and maintain the
batteries voltage and charge during storage or
non-activity.
2.4.6 Earth leakage relay
An earth leakage relay provides protection in case of
an earth leak current. It detects and indicates an earth
fault current and activates the main circuit breaker.
The detection level is set at 30 mA with instantaneous
trip, but it is adjustable in intensity and in trip delay.
2.4.7 Earth pin
The earth pin, to be connected to the ESS’s earth
terminal is located at the bottom of the frame on the
outside.
2.4.8 Remote start connector
X30 .....Remote start connector