- 70 -
10.2 Technical specifications of the ZBE45 unit
ZBE45
Reference conditions Absolute air inlet pressure 1 bar
Relative air humidity 30%
Air inlet temperature 25°C
Performance data Model name ZBE45
Rated frequency 50 Hz
Rated voltage 400/230 VAC
Operating temperature - discharge (min) -20°C
Operating temperature - discharge (max) 50°C
Operating temperature - charge (min) 5°C
Operating temperature - charge (max) 50°C
Altitude capability 3000 m
Relative air humidity maximum 80%
Net energy available 41.4 kWh
Rated energy stored 46 kWh
Rated power 12 kW
Rated apparent power 15 kVA
Rated voltage line to line 400 VAC
Rated current 21 A
Noise pressure in the operator workplace < 70 dB(A)
Battery Voltage 48 V
Life time n° cycles (80% DoD) 2500 cycles
Life time n° cycles (70% DoD) 3000 cycles
Life time n° cycles (50% DoD) 5000 cycles
Maximum Deep of Discharge (DoD) 90%
Discharge autonomy 100% (100 -- 10 SOC) PF = 1 (C1) 3.0 h
Discharge autonomy 75% (100 -- 10 SOC) PF = 1 4.1 h
Discharge autonomy 50% (100 -- 10 SOC) PF = 1 6.2 h
Discharge autonomy 25% (100 -- 10 SOC) PF = 1 13.1 h
Peak power test (t>5s) PF = 1 28 kW
00_00_ZBP45_EN.book Page 70 Monday, October 19, 2020 9:52 AM