EasyManua.ls Logo

Atlas Copco ZBP45 - Page 39

Atlas Copco ZBP45
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 39 -
Inverter overload
Periodic test run
(*) The value measured here will be the total AC
consumption of the system.
Condition-parameters are prioritized in the order
shown above. When a number of conditions are
reached at the same time, only the highest-priority
condition will be shown as active. All enabled
conditions will be evaluated - even if the generator is
already running. When the active condition has been
satisfied, an un-met parameter in a lower-priority
condition will keep the generator running.
Relays triggered by Battery SOC
Use Battery SOC value to start/stop: Toggle this
feature on or off.
Start when Battery SOC is lower than: Set the
depletion level for auto-start.
Start value during quiet hours: During Quiet hours
it may be desirable to delay an auto-start until it
really can't be avoided. If Quiet hours has been
defined, set a lower, more critical, autostart level.
Stop when Battery SOC is higher than: Set the
recharge level for auto-stop.
Stop value during quiet hours: If Quiet hours has
been defined, set a lower auto-stop level to
achieve a shorter generator run-time.
Relays triggered by Battery Current
Use Battery current value to start/stop: Toggle this
feature on or off.
Start when Battery current is higher than: When a
high AC demand is experienced which will soon
exhaust the battery, the generator can be auto-
started to assist in meeting that demand. Set the
current-level at which this will occur.
Start value during quiet hours: If Quiet hours has
been defined, set a higher, more critical current
value.
Start after condition is reached for: Set a delay
before auto-start. Some AC device will draw a
short-term, high-peak current on start-up.
Instigating a delay before auto-start will avoid
starting the generator unnecessarily.
Stop when battery current is lower than: Set the
current for auto-stop.
Stop value during quiet hours: If Quiet hours has
been defined, set a higher current level to achieve
shorter generator run-times.
Stop after condition is reached for: Set a delay to
ensure that the current-reduction condition is
stable.
Relays triggered by Battery Voltage
1 Toggle the feature on or off.
2 When battery voltage falls below the value
entered the relay will start the generator.
3 If Quiet hours has been defined enter a lower
(more critical) value to ensure the generator
will only auto-start when absolutely
necessary.
4 This function allows the user to build-in a
delay between the auto-start condition being
met and an auto-start being triggered. The
importance of this is that a sudden but
temporary high AC demand will cause an
equally sudden drop in battery voltage. This
drop may be temporary - in which case a
generator start is not required.
But if the condition endures for a longer period
of time than the value entered here, the
generator will be started.
5 When battery voltage rises above the value
entered the relay will stop the generator.
6 During Quiet hours it may be desirable to auto-
stop the generator sooner. Enter a lower
battery voltage value than the one above.
00_00_ZBP45_EN.book Page 39 Monday, October 19, 2020 9:52 AM

Table of Contents