6.3.1.18 Error 114 - CPU temperature too
high
This error will reset after the CPU has cooled down.
If the error persists, check the ambient temperature
and check for obstructions near the air inlet and outlet
holes of the charger cabinet. Check manual for
mounting instructions with regard to cooling. If error
persists the CCGX is probably faulty.
6.3.1.19 Error 116 - Calibration data lost
If the unit does not work and error 116 pops up as the
active error the unit is faulty, contact your dealer for
a replacement.
If the error is only present in the history data and the
unit operates normally this error can be ignored
safely. Explanation: when the units power up for the
very first time in the factory, it does not have
calibration data and an error 116 is logged.
Obviously, this should have been cleared, but in the
beginning, units left the factory with this message still
in the history data.
SmartSolar models (not the BlueSolar models):
upgrading to v1.4x firmware is a one-way trip, you
cannot go back to an older firmware version once you
upgrade to v1.4x. Reverting to older firmware gives
error 116 (calibration data lost), this can be fixed by
re-installing the v1.4x firmware.
6.3.1.20 Error 119 - Settings data lost
The charger cannot read its configuration and
stopped.
This error will not auto-reset. To get it working again:
1. Restore it to factory defaults. (top right in Victron
Connect, click on the three dots).
2. Disconnect the charge CCGX from all power-
sources.
3. Wait 3 minutes, and power up again.
4. Reconfigure the charger.