Autoflame Flame Safeguard Overview, Specifications and Wiring
Page | 16
1.2 Installation
When Installing this Flame Safeguard Controller
Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous
condition.
Check the ratings given in the instructions and marked on the product to ensure the product is suitable for
your application.
The installer must be an Autoflame trained, experienced, flame safeguard service technician.
After installation is complete, check out the product operation as detailed in these instructions.
Never update the software on the Flame Safeguard Controller without consulting Autoflame first. Using
wrong software can damage equipment.
Warning
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
To prevent possible hazardous burner operation, perform verification of safety requirements
each time a Flame Safeguard controller is installed on a burner.
IMPORTANT
For on-off gas-fired systems, some authorities, who have jurisdiction, prohibit the wiring of any limit or
operating contacts in series between the flame safeguard control and the main fuel valve(s).
Two flame detectors can be connected if necessary (see the latest Autoflame Flame Scanners Guide)
This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in
accordance with the instructions, may cause interference to radio communications. It has been tested and
found to comply with the limits for a Class B computing device of part 15 of FCC rules, which are designed
to provide reasonable protection against such interference when operated in a commercial environment.
Operation of this equipment in a residential area may cause interference, in which case the users, at their
own expense, may be required to take whatever measures are required to correct this interference.
This digital apparatus does not exceed the Class B limits for radio noise of digital apparatus set out in the
Radio Interference Regulations of the Canadian Department of Communications.
1.2.1. Humidity
The Autoflame Flame Safeguard controller is designed to operate in a maximum 90 percent relative humidity,
continuous, noncondensing moisture environment.
Condensing moisture can cause a shutdown.
1.2.2. Vibration
Do not install the Flame Safeguard controller where it could be subjected to vibration in excess of 0.5G continuous
maximum vibration.
1.2.3. Weather
The Flame Safeguard controller is not designed to be watertight. If installed outdoors it must be protected by an
approved watertight enclosure. See protection rating in section 1.2.4.