Burner Start-Up Sequence
Flame Safeguard (MM80001/FSG) Manual
Page | 122
9.8 Ignition
Figure 9.8.i Run to Ignition
In the Run to Ignition phase shown in Figure 9.8.i, the motor will move to the start position. A start position interlock
is connected to terminal 80; This input must be made to initiate the ignition phase.
In the On/Off burner setup, The T70 (switched neutral) turning off can be used to swap the drive from T81 to T80
(Start Switch) through the relay to initiate the ignition phase.