Burner Start-Up Sequence
Flame Safeguard (MM80001/FSG) Manual
Page | 124
9.9 Pilot
Figure 9.9.i Pilot 1
st
Safety
The pilot gas valve is switched on (open) in the Pilot Open phase shown in Figure 9.9.i. The 1
st
safety time is the
period when the pilot valve is open before the flame is checked. See option/parameter 114.
If no voltage is detected when the pilot valve output T59 should be on (and vice versa), the fault ‘Start Gas Output
Fault’ will occur.