6
MM Features
Mk8 MM Manual
Page | 91
6.4.1
Modbus Address for MM Status (30102)
MM Expansion option 106 sets how Modbus address for MM status (30102) operates. When Expansion Option
106 is set to 1. “Modbus address 30102 shows MM State”. The following values are shown on the table below.
Code
Explanation
1
Recycle
2
Standby
3
Starting
4
Wait Secondary Proving
5
Wait CPI
6
Wait Air Switch
7
Zero Air Sensor
8
Valve Proving
9
Run to Pre-Purge
10
Pre-Purge
11
Run to Start
12
Pre-Ignition
13
Pilot Proving
14
Main Flame Proving
15
Golden Start
16
FGR
17
Firing
18
Moving to low fire to shut down
19
Moving to low fire for COF Changeover
20
COF Changeover
21
Firing on Continuous Pilot Only
22
Run to Post-Purge
23
Post-Purge
24
Post-Firing Valve Proving
255
Fault