Flame Safeguard (MM80001/FSG) Manual
7.3.3
First Out Function
In the First Outs screen, press on the First Out number to be configured and select the function of first out when
upon the active state set for high or low.
Burner continues firing, but the events will be logged.
Burner stops firing and the first out must be reset for the burner to restart.
Burner stops firing and restarts automatically when the input state changes.
Burner continues firing, but the EGA stops sampling.
Burner continues firing, but the EGA trim stops operating.
Used if external stat is optioned.
Figure 7.3.3 Configuring a First Out