Flame Safeguard (MM80001/FSG) Manual
1.6.2
Converting Fireye Flame Safeguard Units
1.6.2.1 Fireye E110:
Firey e
Term inal
# (E110)
Autoflam e
FSG
Term inal #
PRE-IGNITION INTERLOCKS (FUEL VALVE END SWITCH)
RUNNING INTERLOCKS (AIR FLOW SWITCH)
5 SEC EARLY SPARK TERMINATION
OPEN DAMPER PURGE INTERLOCK
OPERATING CONTROL INTERLOCK
1.6.2.2 Fireye Burnerlogix:
Firey e Term inal
#
(BURNERLOGIX )
Autoflam e
FSG
Term inal #
OPERATING CONTROL INTERLOCK
RUNNING INTERLOCKS (AIR FLOW SWITCH)
5 SEC EARLY SPARK TERMINATION
OPEN DAMPER PURGE INTERLOCK
PRE-IGNITION INTERLOCKS (FUEL VALVE END SWITCH)
Notes
1: Any flame sensing device will need to be replaced with an Autoflame sensor. For more details, please see the Autoflame Flame
scanner guide.
2: The pilot configuration may vary for Terminals W, 5 & 6. Check which connects to the ignition transformer.
3: Terminal 60 = Main Fuel Valve 1, Terminal 61 = Main Fuel Valve 2. On Autoflame FSG.
4: Switched neutral output should be connected to neutral side of relay coil.
5: The connections shown assume the use of an Autoflame relay box. Please consult the wiring diagram, if alternative relays are used.