11.2 Lockouts
Lockouts occur when the MM detects a fault with the burner operation such as VPS, gas/air pressure sensor
and flame scanners. The lockout must be cleared and investigated on the MM.
Lockout
Message
Description
1
CPI Input Wrong State
Proof of closure switch opened during ignition sequence
Check wiring on terminal 55
Check proof of closure switches
2
No Air Proving
No air pressure during start/ firing
Check wiring on terminal 54
Check air pressure switch
Check air pressure sensor
Check air pressures during running
3
Ignition Output Fault
Voltage detected when output is off (and vice versa)
Check wiring and voltage on terminal 63
4
Motor Output Fault
Voltage detected when output is off (and vice versa)
Check wiring and voltage on terminal 58
5
Start Gas Output Fault
Voltage detected when output is off (and vice versa)
Check wiring and voltage on terminal 59
6
Main Gas 1 Output Fault
Voltage detected when output is off (and vice versa)
Check wiring and voltage on terminal 60
7
Main Gas 2 Output Fault
Voltage detected when output is off (and vice versa)
Check wiring and voltage on terminal 61
8
Vent Valve Output Fault
Voltage detected when output is off (and vice versa)
Check wiring and voltage on terminal 62
9
Failsafe Relay (Check F1)
Voltage detected when output is off (and vice versa)
Check wiring and voltage on terminal 57
Check fuse 1 (6.3A T) and wiring on terminals 50 64
10
Simulated Flame
Flame is present when it shouldn’t be
Isolate gas/ oil immediately
Call a certified Commissioning Engineer to investigate
If this lockout occurs during shutdown a post-purge may be required for after burn
11
VPS Air Proving Fail
Leak detected during ‘air proving’ part of VPS
Check main fuel valve
Call a certified Commissioning Engineer to investigate
12
VPS Gas Proving Fail
Leak detected during ‘gas proving’ part of VPS
Check option/parameter 133
Check 2
nd
main gas valve and vent valve
Check pilot valve if using single valve pilot
Isolate gas and call a certified Commissioning Engineer to investigate
13
No Flame Signal
No flame detected during ignition/ firing
Visually check flame
Check the flame scanner
Call a certified Commissioning Engineer to investigate
14
Shutter Fault
UV signal detected during shutter operation on self-check
Check wiring on terminals 21 and 22
Check UV scanner type and check option/ parameter 110 is set accordingly
15
NO CPI Reset
Proof of closure switch not made after valves closed
Check wiring on terminal 55 and check proof of closure switches