9
Burner Start-Up Sequence
Flame Safeguard (MM80001/FSG) Manual
Page | 126
Figure 9.9.iii Pilot Proving
The ignition transformer output is switched off after the pilot ignition, in the Pilot Proving phase shown in Figure 9.9.iii.
This proving period gives the pilot flame a chance to stabilise. The flame is checked to ensure the pilot is strong. If
the pilot goes out, the lockout ‘No Flame Signal’ will occur. See option/parameters 115 and 120.