11
Errors & Lockouts
Flame Safeguard (MM80001/FSG) Manual
Page | 141
Lockout
Message
Description
87
Gas Sensor 2 Fault
Internal pressure sensor fault
Contact Autoflame approved local tech centre
88
VPS Air Proving Fail (Fuel 2)
Leak detected during ‘air proving’ part of VPS
Check fuel 2 valve 1
Call a certified Commissioning Engineer to investigate
89
Gas Pressure Low Limit (Fuel 2)
Gas pressure lower than commissioned VPS value
Check gas pressure sensor value
Check option/parameter 136
90
VPS Gas Proving Fail (Fuel 2)
Leak detected during ‘gas proving’ part of VPS
Check option/parameter 133
Check fuel 2 gas valve 1 and vent valve
Check pilot valve if using single valve pilot
Isolate gas and call a certified Commissioning Engineer to investigate
91
Gas Proving Fail High (Fuel 2)
Gas pressure too high during VPS
Isolate gas
Check fuel 2 valve 1 and vent valve
Check option/ parameters 133 and 134
Call a certified Commissioning Engineer to investigate
92
Oil Pressure Too Low (Fuel 2)
Internal fault
Check option/parameter 139
Check oil pressure sensor
93
Gas Pressure Low (Fuel 2)
Gas pressure low limit exceeded while firing (gas sensor)
Check gas pressure
Check option/ parameter 136
94
Oil Pressure Too High (Fuel 2)
Oil pressure above offset upper limit during running
Check option/parameter 140
Check oil pressure sensor
95
Gas Pressure High (Fuel 2)
Gas pressure high limit exceeded while firing (gas sensor)
Check gas pressure
Check option/ parameter 137
96
NO CPI Reset
Proof of closure switch not made after valves closed
Check wiring on terminal 55 and check proof of closure switches
199
Lockout 199
Internal fault
Contact Autoflame approved local tech centre
200
Lockout Cleared
Lockout has been cleared
MM status after lockout has been reset (Modbus)
201
Power up CPU Test Fail
Internal check failed
Contact Autoflame approved local tech centre
202
Power up EEPROM Test Fail
Internal check failed
Contact Autoflame approved local tech centre