EasyManua.ls Logo

Automation Direct Stellar SR55 Series - Page 140

Automation Direct Stellar SR55 Series
202 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 5–14 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 5: Communications
eTherneT/ip neTWork CommuniCaTions (ConTinued)
ConneCTing To The sr55-Cm-eneT module Through i/o (impliCiT messaging)
The connection parameters for Connection 6 (Extended Control) are as follows:
T->O (Input Data) Connection Point Assembly Instance value is 71.
T->O (Input Data) Size is 4 bytes.
The Data format for Status is shown in the “Input Data Setup” screen capture.
O->T (Output Data) Connection Point Assembly Instance value is 21.
O->T (Output Data) Size is 4 bytes.
The Data format for Control is shown in the “Output Data Setup” screen capture.
No Configuration data is required.
To start the SR55, a value of 33 should be placed into Byte 0 of the Control data.
33 equates to Bit 0 (Run Forward) On and Bit 5 (Net Control) On.
To stop the SR55, a value of 32 should be placed into Byte 0 of the Control data.
32 equates to Bit 0 Off and Bit 5 On.
To reset faults on the SR55, a value of 36 should be placed into Byte 0 of the Control data.
36 equates to Bit 2 (Fault Reset) On and Bit 5 (Net Control) On.
The following images are an example setup of I/O (Implicit Messaging) to the SR55 EtherNet/IP
adapter from a Productivity Series CPU.
inpuT daTa seTup

Table of Contents

Related product manuals