Page 2–8 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 2: Electrical Installation
ConTrol CirCuiT Wiring
1) The programmed digiTal inpuT seTTings for d1com, d1-1i, d1-2i, and d2com, d2-1i
musT correspond To The volTage applied To These Terminals To avoid risk of damage To The
equipmenT.
2) The conTrol supply can be 110 To 230vac applied To The n, l Terminals or 24vdc applied To
The 0vdc, 24v inpuT Terminals. The correcT volTage as specified musT only be applied To
one of These supply inpuTs To avoid risk of damage To The equipmenT.
Three-Wire ConTrol
24VDC control supply and
digital input programming
24
VDC
D1-2ID1-1I D2-1I 33
0VDC D2COMD1COM 34
K1
!
3-Wire Control Diagram
110/230VAC control supply
and digital input programming
L D1-2ID1-1I D2-1I 33
N D2COMD1COM 34
K1
!
110/230VAC
N
24VDC
0VDC
Emergency StopEmergency Stop
Digital Output
Configuration
34 = DO3 set to
“Running”
(This pulls in the
line contactor,
K1, before the
ramp starts)
Digital Input
Configuration
D1-1I = Start
D1-2I = Stop
D2-1I = Reset
power facTor correcTion capaciTors* musT noT be posiTioned beTween The sofT sTarTer and The
moTor, or There is a risk of damaging The ThyrisTors due To currenT peaks.
user-programmable ConTrol
User Programmable Control Diagram
L
D1-1I
Stop
Start
D2-1I 33
N
D2COMD1COM 34
K1K2
K2.1
K2.2
1)
!
24
VDC
0VDC
D1-1I
Stop
Start
D2-1I 33
D2COMD1COM 34
K1K2
K2.1
K2.2
1)
!
110/230VAC
24VDC
0VDC
N
Emergency StopEmergency Stop
1) Optional high reset. If this reset is required, ensure that “User Programmable” is selected as the control method menu
found in the Digital Inputs menu. If you would prefer the reset to work by removing and reapplying the Start Signal on
D1-1I then select “Two wire control” in the control method menu.
Digital Input Configuration
D1-1I = High Start / Low Stop
D1-2I = None
D2-1I = High Reset
Digital Output Configuration
34 = DO3 set to “Running”
(This pulls in the line contactor,
K1, before the ramp starts)
* Note: Power factor correction capacitors (PFCs) can reduce a facility’s kVAR charges in some
cases. Determining the need for, and location of, PFCs should be performed by a qualified
engineer (from your utility company or a power quality engineering firm). PFCs cannot be
located between the SR55 and the motor.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals